901 4 6 2 marking on access doors.
Fire riser room door requirements.
That is the only project that i know of that has it in the stairwell.
Doors to any fire protection electrical or mechanical equipment rooms shall be marked from the exterior.
Access doors for automatic sprin kler system riser rooms and fire pump rooms shall be labeled with an approved sign.
What s new is fire pumps controllers and risers shall be readily accessible within the room and to those who access the room.
Fire protection equipment access signs sprinkler room fire pump room fire pump test valve etc should be marked with white letters on a red background.
A 1 1 see annex k for general information about fire doors.
The lettering shall be in a contrasting color to the background.
Letters shall have a minimum height of 2 inches 51 mm with a minimum stroke of 3 8 inch 10 mm.
Fire equipment room minimum requirements fire riser room the fire equipment room shall be located within the building footprint.
1 1 1 with the exception of fabric fire safety curtain assemblies this standard addresses assemblies that have.
Cated in a fire pump room or automatic sprinkler system riser room the door shall be permitted to be locked provided the key is available at all times.
The international codes i codes are the widely accepted comprehensive set of model codes used in the us and abroad to help ensure the engineering of safe sustainable affordable and resilient structures.
Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign.
Door marking requirements code section.
If the room has a lock then the.
Fire pump and fire sprinkler riser rooms ifc ibc 901 4 6 the section in the 2018 ifc for rooms that house fire sprinkler risers and fire pumps is expanding.
The fire sprinkler riser assembly the fire alarm control panel fire alarm manual pull station spare sprinkler heads storage box and the document box for as built drawings shall be located within the room.
I was going to add that i have heard of one project that our office designed and the fpe that the contractor hired put the fire riser in the stairwell and got approved by the state fire marshal.
Fire pumps may also be kept within the riser room though the room will then have to meet the more robust construction requirements for pump rooms as set by nfpa 20 fire protection storage cabinet often the riser room serves as an ideal location to store spare sprinkler heads compatible sprinkler wrenches copies of relevant nfpa codes.